Cart  

product (empty)

Manufacturers

Advertising

KYORITSU 6010A Multifunction Tester

KYORITSU 6010A Multifunction Tester
Continuity and Insulation Testing ; Loop and RCD Testing.

More details

$510.00 tax incl.

Availability: Shipping to Worldwide

Add to cart

Features:

Continuity and Insulation Testing

  • Live circuit warning LED:
    Immediate illumination of a warning lamp if the circuit under test is live
  • Auto Discharge:
    Allows fast and safe discharge of electrical energy stored in capacitive circuits following testing
  • Integral overload protection on internal continuity and insulation test circuitry
  • Autoranging
  • 500V DC test voltage for insulation tests
  • 200mA short circuit current on continuity ranges   

Loop and RCD Testing

  • Wiring connection check LED’s:
    Immediate indication if wiring of circuit under test is correct
  • Overheat Protection:
    Rapid detection of overheating of internal circuitry,display of warning signal to user and automatic halting of measurement
  • Supply Voltage Indication:
    Can display supply voltage value in loop impedance mode
  • Low Current Loop Impedance Test:
    Short duration low test current will prevent tripping of many passive RCDs
  • Auto Data Hold:
    Retains displayed reading for set period following test
  • Phase Angle Selection:
    Selection of test current from +ve or -ve half cycle of waveform can prevent tripping of polarized type RCDs 

Specification:

Continuity Testing
Measuring Ranges 0~19.99 and 10.0~199.9Ω (2 auto ranges)
Open Circuit Voltage > 4V (as per IEC 364)
Short Circuit Current > 200mA DC (as per IEC 364)
Accuracy |±(3% + 3dgt)
Loop Impedance Testing
Rated Voltage 230V AC +10%-15% (50Hz)
Voltage Measuring Range 100-250V AC (50Hz)
Impedance Range 20/2000Ω
Nominal Test Current 25A (20Ω range) 15mA (2000Ω range)
Test Period 1/2 cycle (10ms)
Accuracy 20Ω range : ±(3% + 8dgt)   2000Ω range : ±(3% + 8dgt)
Insulation Testing
Measuring Ranges 0~19.99 and 10.0~199.9MΩ (2 auto ranges)
Test Voltage 500V DC
Output Voltage on 570V DC±6%
Open Circuit
Rated Current > 1mA (as per IEC 364)
Accuracy |± (3% + 3dgt)
RCD Testing
Rated Voltage 230V AC +10%-15% (50Hz)
Trip Current Settings RCD × 1/2: 5, 15, 50, 150, 250mA
RCD × 1: 10, 30, 100, 300, 500mA
Trip Current Duration RCD × 1/2 × 1: 2000ms
Fast Trip 150mA
Accuracy Trip current ±3% of test current at 230V.
Trip time ±(3% + 3dgt)
General
Safety Standard IEC 61010-1 CAT.III 300V Pollution Degree 2
IEC 61010-2-031
IEC 61557
Withstand Voltage 4000V AC for 1 minute
Power Source R6P (AA) (1.5V) × 8
Dimensions 175(L) × 115(W) × 86(D)mm
Weight 780g approx.
Accessories 7025 (Test Leads) 
KAMP10* (Test Lead with IEC Connector)
Pouch for Test leads
Shoulder Strap
Shoulder Pad
R6P (AA) × 8
Instruction Manual
Optional 7133A

trDimensions

Specials

  • $0.00 $0.00

PayPal